CANTHERM
  Thermal Cutouts  
 

< Back to Thermal Cutouts

 Protection For Coils / Windings    PDF

B12 / B13 (Double Contacts)
This thermostat operates as a thermal cutout. A thermally sensitive bimetal snap-element with double contacts either opens or closes an elecrtical circuit by switching at a pre-set response temperature. Reset follows automatically after a considerable drop in temperature.

Applications Single Phase Motors, Generators, Convertors, Transformers, Pumps, Heating Elements, Signal Transmitters, Fire Detectors, Magnets, Relays, Chokes, Coils, Power Supplies, Inverters

 

> Technical Data
ratings
B12A / E
B12B / G
B13N / T
version

normally closed
Cantherm Code=2

normally open
Cantherm Code=1
normally closed / open
rated current at 250 V 50/60 Hz
(cos 0.95/0.6)
6.3 A / 6.0 A
10.0 A / 6.0 A
13.0 A / 6.0 A
5.0 A / 1.6 A
1...100 mA (24 Vdc)
switching cycles under rated current
10,000
5,000
1,000
5,000
10,000
max. current at 250 V 50/60 Hz
(cos 0.95)
30.0 A
-
switching cycles under max. current
100
-
temperature rating Ta (steps in 5 K)
70°C...160°C
70°C...155°C
70°C...160/155°C
tolerances
standard:+/- 5 K
feature of automatic action
1.B.M, 2.B, 1.C
1.B
-
contact resistance
( incl. wire of 100 mm )
< 50 mΩ
hysteresis
30 K ± 15 K 1
dielectric strength
( standard insulation )
2 kV
shock- / vibration testing
( similar to EN 50155 )
400 m/s2 sine half wave / 100 m/s2 5 Hz ... 2,000 Hz sine
resistances to impregnation
tight against ordinary resins and lacquers
degrees of protection provided by enclosures ( EN 60529 )
IP00
suitable for use in protection category
I, II
-
approvals
VDE / ENEC
EN 60730-1 / -2-3 2) /-2-9
no approval
required to
voltage ratings
lower than
42 V
UL
UL 2111 / UL 873 3)
CSA / cUL
C22.2 No. 77 / C22.2 No. 24 3)
CQC
GB14536.1-1998 / GB14536.10-1996 3)
1) at the Ta (upper and lower) limits the hysteresis could deviate
2) different power rating
3) details on request

 

> Standard wire ( length 100 ± 10 mm, stripped 6 ± 1 mm )
lead
Cantherm
code
MIC
code
temp. max.
operating voltage max.
diameter insulation
cross section diameter 2)
UL style
black
ACDA1)
L3001)
150° C
300 V
1.57 mm
AWG24 / 0.24 mm2)
3398
yellow
AEDC
L310
1.80 mm
AWG20 / 0.48 mm2)
black
AFDA
L320
2.15 mm
AWG18 / 0.96 mm2)
white
LCDB1)
L3301)
200° C
600 V
0.90 mm
AWG24 / 0.24 mm2)
3557
white
LEDB
L340
1.26 mm
AWG20 / 0.61 mm2)
white
LFDB
L350
1.50 mm
AWG18 / 0.96 mm2)
black
ASDA
L410
150° C
300 V
1.65 mm
AWG20 / 0.81 mm
3398
white
DEDB
L440
200° C
300 V
1.51 mm
AWG20 / 0.81 mm
1332
1) B13 only
2) AWG20 is recommended

 

> Standard insulation
control type
nc
no
Cantherm
code
MIC
code
illust.
drawing dimensions (mm)
technicals specification
approvals1)
B12

A

B

Class B
U103 | C


Class F
U107 | G

U253
 
 
MIC Version Shown
shrink cap
potted
VDE,UL, cUL
B13
N
T
B12
A
B
U155 | X

U186 | 3
U186
 

 

cap of PPS
potted
VDE, UL, cUL
B13
N
T

 

> Specific variations      U= Insulation G= Housing
control type
nc
no
Cantherm
code
MIC
code
illust.
drawing dimensions (mm)
technicals
specification
approvals1)
B12

A

B
none | 0
 
 
not insulated
potted
VDE,UL,
cUL, CSA
B13
N
T
B12
A
B
U112 | L
U112
 

 

epoxy coated
VDE, UL, cUL
B13
N T
B12
A
B
U294 | 7
U294
housing of PPS
potted
VDE, UL, cUL
B13
N
T
B12
A
B
Wire
A800 | IZA
A800
not insulated
potted
VDE, UL, cUL
B13
N
T
B12
E
G
G702 | C
G402
aluminum housing
thread M4x6
potted

Ta max. 150†C
VDE, UL, cUL
B13
N
T
B12
E
G
G714 | F
G714
brass housing
thread M4x5
potted

Ta max. 150†C
VDE, UL, cUL
B13
N
T

1) B12 only

 

 > Heating by current

The diagram is measured with a thermal control without any insulation in an oil bath.

Attention:
The heating depends on the thermal conduction of the control to the equipment or part which should be
protected.

 

 > Ordering & Marking Example
MIC Ordering Example  B12A12005L310100U253 ]
B12 A 120 05 L310 100 U253
type normally closed temperature tolerance
+/-5°C
lead wire white, AWG20
UL3398
length 100 mm shrinkcap insulation

Cantherm Ordering Example  B1212025AEDCC0E ] standard version
B12 120 2 5 AE D C C O E
type temperature normally closed tolerance +/-5°C wire leads UL3398 20 AWG length
D=4"
color yellow insulation U103

housing - none

strip .25"

Marking
B12A type (B12 nc)

12005 response temperature (120°C), tolerance (± 5K)

049D date of manufacture (April 2009), country (D = Germany)

 
CANTHERM
(800) 561-7207 | sales@cantherm.com